Light control menu

The Light control menu lets you set up light activation for a specific parti tion.

Note:

For light control to work you must power the panel with a power line carrier

transformer and X10 powerhouse lamp modules must be installed at desired
lamps.

Light control - partition 1 to 6 settings

Entry lights

Shortcut: 0400 to 0450

Default: None

This setting determines which X10 controlled lights turn on during
entry and exit delays.

The X10 lamp modules set to 1 always turn on during the entry and
exit delays. X10 lamp modules set to 2 always flash the arming level
when arming the system. For example, lights flash two times when
arming to stay (Level 2), and three times when arming to away
(Level 3).

To set the entry lights:

1. With the desired partition selected, press #. The display shows

ENTRY LIGHTS nnnnnnn

(current setting).

2. Enter all the desired light numbers (3 to 9) based on the unit dial
setting on each X10 lamp module.

3. The display flashes the entered settings. Press #

and the display

shows the new settings.

To delete entry lights, enter any light number that appears on the
display, then press #. The number disappears from the display.

House code

Shortcut: 0401 to 0451

Default: 01 B, 02 C, 03
D, 04 E, 05 F, and 06
G

This setting enables X10 controlled lights to work in a selected
partition without interfering with the X10 controlled lights of the other
partitions. After setting the panel house code for each partition, you
must set the X10 controlled lights for that partition to the same
house code. The letter that appears automatically after the house
code number indicates the necessary house dial setting for X10
modules in that partition (1 to 255).