Chapter 4: Testing and troubleshooting

110

Concord 4 Installation Manual

The negative red lead or (RING) wires must connect to terminal 28 on the
board.

2.

Concord panels are voltage sensitive, so it’s necessary to check for proper
voltage:

On hook voltage should be approximately 48-52 volts.
Off hook voltage should be approximately 6-10 volts.

Note:

The Concord panel has a built-in line voltage meter. If it does not see

proper voltage, it will not dial on a tone phone line. This does not apply to a pulse
phone line.

To check proper phone line with line seizure:

1. Check the type of phone line. Concord panels work with analog phone lines

or DSL with a DSL filter inline to the panel. VOIP or digital phone lines may
not work with the panels.

2.

Check that the premise’s phone line is working.

3. Check that the DB-8 cord is plugged into the RJ31X/CA-38A jack.

4. Check for correct phone line wiring between the TELCO block and the

RJ31X/CA-38A jack.

Alphanumeric touchpad issues

Display shows all ************.

Touchpad is not connected to panel bus terminals or is wired incorrectly. Check
and correct wiring.

Display is blank.

• Check that panel is powered up.

• Check for touchpad power and/or incorrect bus wiring, opens, or shorts.

• Check the touchpad brightness setting. (See Options menu on page 108.)

Touchpad buttons don’t beep when pressed.

• Check for touchpad power and/or incorrect bus wiring, opens, or shorts.

• Check that key beeps option is set to on. (See the Accessory modules - bus

device settings on page 93.)

Fixed display touchpad issues

Display is lit but does not respond to key presses.