Chapter 2: Installation

Concord 4 Installation Manual

15

Intrusion detection devices

Figure 6 below shows the typical wiring for NC and NO door/window intrusion
detection and the typical wiring for a PIR motion detector. The minimum available
panel voltage for hardwired PIR motion detectors is 8.5 VDC.

Figure 6: Connecting intrusion detection and motion detector circuits

Panel terminals

Normally closed
(NC) contacts
in series

2 kohm resistor

Normally open
(NO) contacts
in series

2 kohm resistor

Motion
detector

GND

ZONE1 ZONE2

GND

ZONE3

+12V

GND

ZONE5

NC COM

Smoke detectors

You can connect two-wire and four-wire smoke detectors to the system.

Two-wire smoke detectors

Zone input 8 can be set up (in program mode) to accept the following 12 VDC,
two-wire smoke detectors:

ESL models 429AT, 429C, 429CT, 521B, 521BXT, 521NCSXT (models
521B and 521BXT require the following dip switch settings: 1-on, 2-off)

Caution:

Use only the two-wire smoke detector models listed. Alarm signals from

other detectors may not process correctly if the panel loses AC power and is
operating only from the backup battery.

When set up for two-wire smoke detectors, zone 8 can handle up to 20 smoke
detectors (all of the same model, as listed above) with 120 uA maximum idle
current per detector. Maximum total loop current allowed in an alarm condition is
90 mA. Connect one or more, two-wire smoke detectors to the panel as shown in
Figure 7 on page 16.