Chapter 5 Parameters|VFD-S Series

5-46

Revision August 2006, SE08, SW V2.61

d29 M0: 0: RUN 1: STOP, M1: no function, Direction is controlled by keypad

RUN/STOP

M0 "Open": Stop, "Close": Run

M1 No Function

GND

4-09

Line Start Lockout

Factory Setting: d0

Settings

d0

Disable

d1

Enable

When enabled, the AC drive will not start when powered up with run commands applied. To

start in Line Start Lockout mode, the AC drive must see the run command go from stop to run

after power up. When Line Start Lockout is disable (also known as Auto-Start), the drive will

start when powered-up with run commands applied.

4-10

Up/Down Mode

Factory Setting: d0

Settings

d0

Based on accel/decel time

d1

up frequency according to constant speed, down frequency
according to deceleration time

d2

up frequency according to acceleration time, down frequency
according to constant speed

d3

Constant

speed

4-11

Accel/Decel Rate of Change of UP/DOWN Operation

with Constant Speed

Unit: 5

Settings

d0 to d1000 Hz/sec

Factory Setting: d1

This parameter is used to set the acceleration/deceleration speed mode when multi-function

terminal is set to up/down frequency. (Pr. 4-04 ~ Pr.4-08, function d15, d16)