Chapter 5 Parameters|VFD-S Series

Revision August 2006, SE08, SW V2.61

5-61

8-15

Automatic Voltage Regulation (AVR)

Factory Setting: d0

Settings

d0

AVR function enabled

d1

AVR function disabled

d2

AVR function disabled when deceleration

AVR function automatically regulates the AC drive output voltage to the Maximum Output

Voltage (Pr.1-02). For instance, if Pr.1-02 is set at 200 VAC and the input voltage is at 200V

to 264VAC, then the Maximum Output Voltage will automatically be reduced to a maximum of

200 VAC.

Without AVR function, the Maximum Output Voltage may vary between 180V to 264VAC, due

to the input voltage varying between 180V to 264 VAC.

Selecting program value d2 enables the AVR function and also disables the AVR function

during deceleration. This offers a quicker deceleration.

8-16

Software Braking Level

Unit: 1

Settings

230V series: d350 to d450V

Factory Setting: d380

460V series: d700to d900V

Factory Setting: d760

During deceleration, the DC-bus voltage will increase due to motor regeneration. When DC

bus voltage level exceeds the Software Braking Level, the DC brake output pins (B1, B2) will

be activated.

8-17

Lower Bound of DC Braking Start-up Frequency

Unit: 0.1

Settings

d0.0 to d400 Hz

Factory Setting: d0.0

The setting frequency is lower than Pr.8-17, the DC Braking will not be activated when stops.