Chapter 5 Parameters|VFD-S Series

Revision August 2006, SE08, SW V2.61

5-63

9-03

Time-out Detection

Factory Setting: d0

Settings

d0

Disable

d1

1

sec

d2

2

sec

:

d20

20

sec

If this function is enabled, the timer will start counting once the first valid Modbus

communication signal is received after power-up or reset. The timer will reset to 0 after each

valid Modbus communication message is received. If the watchdog timer reaches the value

set in Pr. 9-03, the drive will stop its output and display the message "CE10" on the digital

keypad. This fault can reset by an external terminal, keypad or a Modbus communication

reset command.

9-04

Communication Protocol

Factory Setting: d0

Settings

d0

Modbus ASCII mode, protocol <7,N,2>

d1

Modbus ASCII mode, protocol <7,E,1>

d2

Modbus ASCII mode, protocol <7,O,1>

d3

Modbus ASCII mode, protocol <8,N,2>

d4

Modbus ASCII mode, protocol <8,E,1>

d5

Modbus ASCII mode, protocol <8,O,1>

d6

Modbus RTU mode, protocol <8,N,2>

d7

Modbus RTU mode, protocol <8,E,1>

d8

Modbus RTU mode, protocol <8,O,1>

1. Computer Control

6

1

1: +EV
2: GND
3: SG-
4: SG+

There is a built-in RS-485 serial interface, marked (RJ-11 Jack) on the control terminal

block, for VFD-S Series. The pins are defined above. Each VFD-S AC drive has a pre-

assigned communication address specified by Pr. 9-00. The computer then controls

each AC drive according to its communication address.

VFD-S can be setup to communicate on Modbus networks using one of the following

modes: ASCII (American Standard Code for Information Interchange) or RTU (Remote