Chapter 5 Parameters|VFD-S Series

Revision August 2006, SE08, SW V2.61

5-53

DC bus voltage

time

Over-voltage
detection
level Pr.6-01

Output
Freq.

time

Over-voltage Stall Prevention

Band=20V

6-02

Over-Current Stall Prevention Level

Unit: 1

Settings

d20 to d150%

Factory Setting: d130

A setting of 100% is equal to the Rated Output Current of the drive.

During acceleration and steady-state operation, the AC drive output current may increase

abruptly to exceed the value specified by Pr.6-02 due to rapid acceleration or excessive load

on the motor. When this function is enabled, the AC drive will decrease. The AC drive will only

resume acceleration when the current drops below the level specified by Pr. 6-02.

Output current

Over-current
detection
level
Pr.6-02

time

Output
frequency

time

Over-current Stall Prevention Level

ON

OFF

Band=5%