Delta Electronics AC Motor Drive VFD007S23A User Manual

Page 70

Advertising
background image

Chapter 5 Parameters|VFD-S Series

Revision August 2006, SE08, SW V2.61

5-15

Output Signal during Running

Applications Purpose

Functions

Related

Parameters

General application

Provide a signal for
running status

Signal available to stop braking (brake
release) when the AC motor drive is
running. (This signal will disappear
when the AC motor drive is free-
running.)

3-05~3-06

Output Signal in Zero Speed

Applications Purpose

Functions

Related

Parameters

General application

Provide a signal for
running status

When the output frequency is lower
than the min. output frequency, a
signal is given for external system or
control wiring.

3-05~3-06

Output Signal at Desired Frequency

Applications Purpose

Functions

Related

Parameters

General application

Provide a signal for
running status

When the output frequency is at the
desired frequency, a signal is given for
external system or control wiring.

3-05~3-06

Over-torque Detection

Applications Purpose

Functions

Related

Parameters

Pumps, fans and
extruders

To protect
machines and to
have continuous/
reliable operation

The over-torque detection level can be
set. Once over-torque occurs, a signal
will occur to prevent the AC motor
drive damage.

3-05~3-06

6-04

6-05

Output Signal at Low-voltage

Applications Purpose

Functions

Related

Parameters

General application

Provide a signal for
running status

When the voltage between P-N is low
voltage, a signal is given for external
system or control wiring.

3-05~3-06