4 control terminals, 4 control terminals -24 – Delta Electronics AC Motor Drive VFD007S23A User Manual

Page 37

Advertising
background image

Chapter 2 Installation and Wiring|VFD-S Series

2-24

Revision August 2006, SE08, SW V2.61

2.4.4 Control Terminals

Control Terminal Wiring (Factory Setting)

A. XXXSXXA/B/D/U

RA

M1

AVI

10V

+

AFM M0

M4

M2 M3

M5

GND

RB
RC

MO1

MCM

RJ11

Multi-step speed 3

Multi-step speed 2

Multi-step speed 1

Reset

Reverse/Stop

Forward/Stop

Corrector

potentiometer

VR : 1K~5K

Freq. meter

0~10 VDC

Full scale voltmeter

Operation freq.
setting

potentiometer

VR : 3K~5K

Relay contactor output
Factory setting : Fault indication

Photo coupler output

Factory setting : in work

6 ~ 1

RS485 Communication port

B. XXXSXXE

Multi-step speed 3

*

*

Terminal symbols and functions

Terminal

Symbol

Terminal Function

Factory Settings (NPN mode)

ON: Connect to GND

M0

Multi-function auxiliary input

M1

Multi-function input 1

M2

Multi-function input 2

M3

Multi-function input 3

Refer to Pr.4-04 to Pr.4-08 for programming the
Multi-function Inputs.
ON: the activation current is 16mA.
OFF: leakage current tolerance is 10μA.

Wire Gauge: 24-12 AWG
Wire Type: Copper Only
Torque: 4 kgf-cm (3.5 in-lbf)

Wire Gauge: 24-16 AWG
Wire Type: Copper Only
Torque: 2 kgf-cm (1.7 in-lbf)