Chapter 5 Parameters|VFD-S Series

5-52

Revision August 2006, SE08, SW V2.61

Group 6: Protection Parameters

6-00

Over-Voltage Stall Prevention

Unit: 0.1

Factory Setting: d1

Settings

d0

Disable

d1

Enable

During deceleration, the motor DC bus voltage may exceed its Maximum Allowable Value due

to motor regeneration. When this function is enabled, the AC drive will stop decelerating.

Maintaining a constant output frequency when it happens. The AC drive will only resume

deceleration when the voltage drops below preset value.

NOTE

With a moderate inertial load, the over-voltage during deceleration won’t happen, and the drive will

stop in programmed time. The AC drive will automatically extend the deceleration time with high

inertial loads. If deceleration time is critical for the application, then dynamic braking resistors should

be used.

6-01

Over-Voltage Stall Prevention Level

Unit: 1

Settings 230V Series d350 to d410V

Factory Setting: 390

460V Series d700 to d820V

Factory Setting: 780

During deceleration, the DC bus voltage may exceed its maximum allowable value due to

motor regeneration. When this function is enabled, the AC drive will stop decelerating.

Maintaining a constant output frequency when it happens. The AC drive will resume

deceleration when the voltage drops below preset value.

With a moderate inertial load, the over-voltage during deceleration won’t happen, and the

drive will stop in programmed time. The AC drive will automatically extend the deceleration

time with high inertial loads. If deceleration time is critical for the application, then dynamic

braking resistors should be used.