Delta Electronics AC Motor Drive VFD007S23A User Manual

Page 117

Advertising
background image

Chapter 5 Parameters|VFD-S Series

5-62

Revision August 2006, SE08, SW V2.61

Group 9: Communication Parameters

9-00

Communication Address

Settings

d1 to d254

Factory Setting: d1

If the AC drive is controlled by RS-485 serial communication, the communication address

must be set via this parameter.

S1

Computer

S1

S1

RS485

d1

d3

d2

9-01

Transmission Speed

Factory Setting: d1

Settings

d0

Baud rate 4800 bps (bits / second)

d1

Baud rate 9600 bps

d2

Baud rate 19200 bps

d3

Baud rate 38400 bps

Users can set parameters and control the operation of the AC drive via the RS-485 serial

interface of a personal computer. This parameter is used to set the transmission speed

between the computer and AC drive.

9-02

Transmission Fault Treatment

Factory Setting: d0

Settings

d0

Warn and keep operating

d1

Warn and RAMP to stop

d2

Warn and COAST to stop

d3

No warning and keep operating