Chapter 5 Parameters|VFD-S Series

Revision August 2006, SE08, SW V2.61

5-23

This parameter sets the Mid-Point Voltage of any V/f curve. With this setting, the V/f ratio

between Minimum Frequency and Mid-Point Frequency can be determined. This parameter

must be equal to or greater than Minimum Output Voltage (Pr.1-06) and equal to or less than

Maximum Output Voltage (Pr.1-02).

1-05

Minimum Output Frequency (Fmin)

Unit: 0.1

Settings

d1.0 to d60.0Hz

Factory Setting: d1.0

This parameter sets the Minimum Output Frequency of the AC drive. This parameter must be

equal to or less than Mid-Point Frequency (Pr.1-03).

1-06

Minimum Output Voltage (Vmin)

Unit: 0.1

Settings

115V/230V

series d2.0

to d255V

Factory Setting: d12.0

460V series

d4.0 to d510V

Factory Setting: d24.0

This parameter sets Minimum Output Voltage of the AC drive. This parameter must be equal

to or less than Mid-Point Voltage (Pr.1-04).

Voltage

Pr.1-02

Pr.1-04
Pr.1-06

0

Pr.1-03
Pr.1-05

Pr.1-00
Pr.1-01

Freq.

Standard V/F Curve

1-07

Output Frequency Upper Limit

Unit: 1

Settings

d1 to d110%

Factory Setting: d100

This parameter must be equal to or greater than the Output Frequency Lower Limit (Pr.1-08).

The Maximum Output Frequency (Pr.1-00) is regarded as 100%.

Output Frequency Upper Limit value = (Pr.1-00 * Pr.1-07)/100.

1-08

Output Frequency Lower Limit

Unit: 1

Settings

d0 to d100%

Factory Setting: d0

The Upper/Lower Limit is to prevent operation error and machine damage.