Chapter 5 Parameters|VFD-S Series

5-26

Revision August 2006, SE08, SW V2.61

1-16

Acceleration S-Curve

1-17

Deceleration S-Curve

Settings

d0 to d7

Factory Setting: d0

These two parameters allow you to configure whether the acceleration and/or deceleration

ramps are linear or S-shaped. The S-curve is enabled when set at d1-d7. Setting d1 offers

the quickest S-curve and d7 offers the longest and smoothest S-curve. The AC drive will not

follow the acceleration/deceleration time in Pr.1-09 to Pr.1-12. To Disable the S-curve, set

Pr.1-16 and Pr.1-17 to d0.

From the diagram shown below, the original setting acceleration/deceleration time will be for

reference when the function of the S-curve is enabled. The actual acceleration/deceleration

time will be determined based on the S-curve selected (d1 to d7).

3

1

2

4

1

3

4

2

1 2

3 4

Disable S curve

Enable S curve

Acceleration/deceleration Characteristics

1-18

Jog Decelerating Time

Unit: 0.1Sec

Settings

d0.0 to d600

Factory Setting: d0.0

When Pr.1-18 is set to d0.0 Jog decelerating time determined by the setting of Pr.1-13 0.1 to

600 sec, Jog decelerating time can be set independently, separates from Pr.1-13.

When Pr.1-18 is set to 0.0, Pr.1-13 determines both Jog acceleration and deceleration time.

When Pr.1-18 is set between 0.1 to 600 seconds, which will determine Jog Decelerating Time

and Pr.1-13 will only determine Jog Accelerating Time.