Delta Electronics AC Motor Drive VFD007S23A User Manual

Page 63

Advertising
background image

Chapter 5 Parameters|VFD-S Series

5-8

Revision August 2006, SE08, SW V2.61

Pr. Explanation

Settings

Factory

Setting

NOTE

6-05

Over-Torque Detection Time

d0.1 to d10.0 Sec

d0.1

6-06

Electronic Thermal Overload Relay
Selection

d0 to d2

d2

6-07

Electronic Thermal
Characteristic

d30 to d600 Sec

d60

d0: No fault
d1: Over current (oc)
d2: Over voltage (ov)
d3: Over heat (oH)

6-08


Present Fault Record

d4: Over load (oL)
d5: Over load (oL1)
d6: External fault (EF)

6-09

Second Most Recent Fault Record

d7: Reserved
d8: Reserved
d9: Excess current during

acceleration (ocA)

d10: Excess current during

deceleration (ocd)

d11: Excess current during steady

state (ocn)

6-10 Third Most Recent Fault Record

d12: Ground fault (GF)

d0

d13:

Reserved

d14: Low voltage (Lv)

d15: CPU failure 1 (cF1)

d16: CPU failure 2 (cF2)

d17: Base block (b.b.)

d18: Overload (oL2)

d19: Auto acceleration/deceleration

failure (cFA)

d20: Software protection enable

(codE)

d21:

Reserved

d22: CPU failure (cF3.1)

d23: CPU failure (cF3.2)

d24: CPU failure (cF3.3)

d25: CPU failure (cF3.4)

d26: CPU failure (cF3.5)

d27: CPU failure (cF3.6)

d28: CPU failure (cF3.7)

d29: Hardware protection failure

(HPF.1)

d30: Hardware protection failure

(HPF.2)

d31: Hardware protection failure

(HPF.3)

d32: Communication time-out

(CE10)

d33:

Reserved

d34: Software error (SErr)

d35: Reserved

d36: PID error (Pld)

d37: Reserved

d38: Phase loss (PHL)

d0

Advertising