3khz 10khz – Delta Electronics AC Motor Drive VFD007S23A User Manual

Page 84

Advertising
background image

Chapter 5 Parameters|VFD-S Series

Revision August 2006, SE08, SW V2.61

5-29

RUN

STOP

RUN

STOP

Frequency

Frequency

Time

Time

output
frequency

output
frequency

motor
speed

motor
speed

operation
command

operation
command

stops according to
decel eration time

free run to stop

ramp to stop and free run to stop

2-03

PWM Carrier Frequency Selections

Unit: 1

115V/230V/460V Series

Power

0.25 to 3hp (0.2kW to 2.2kW)

Setting Range

d3 to d10 kHz

Factory Setting

d10 kHz

This parameter determines the PWM carrier frequency of the AC motor drive.

3kHz

10kHz

Carrier
Frequency

Acoustic
Noise

Electromagnetic
Noise or leakage
current

Heat
Dissipation

Current
Wave

Significant

Minimal

Significant

Minimal

Minimal

Significant

Minimal

Significant

From the table, we see that the PWM carrier frequency has a significant influence on the

electromagnetic noise, AC motor drive heat dissipation, and motor acoustic noise.

2-04

Motor Direction Control

Factory Setting: d0

Settings

d0

Enable forward/reverse operation

d1

Disable reverse operation

The parameter determines whether the AC drive can operate in the reverse direction.