Chapter 5 Parameters|VFD-S Series

Revision August 2006, SE08, SW V2.61

5-25

The JOG function can be selected using Multi-function Input terminals (Pr.4-04 to Pr.4-08) if

programmed for Jog (d10). When the Jog terminal is “closed”, the AC drive will accelerate

from Minimum Output Frequency (Pr.1-05) to Jog Frequency (Pr.1-14). When the Jog

terminal “open”, the AC drive will decelerate from Jog Frequency to zero. The

acceleration/deceleration time is decided by the Jog acceleration/deceleration time (Pr.1-13).

During operation, the AC drive cannot perform Jog command. And during Jog operation,

other operation commands cannot be accepted, except command of FORWARD, REVERSE

and STOP keys on the digital keypad.

Frequency

Max.
Output
freq.
Pr.1-00

Jog
Freq.
Pr.1-14

Acceleration Time

Deceleration Time

Time

Jog operation
command

ON

OFF

Pr. 1-13

Pr. 1-13

1-15

Auto-Acceleration / Deceleration

Factory Setting: d0

Settings

d0

Linear

Accel/Decel

d1

Auto Accel, Linear Decel

d2

Linear Accel, Auto Decel

d3

Auto Accel/Decel (Set by load)

d4

Linear Accel; Auto Decel, Stall Prevention during Decel

d5

Auto Accel/Decel, Stall Prevention during Decel

If the auto acceleration/deceleration is selected, the AC drive will acceleration/deceleration in

the fastest and smoothest means possible by automatically adjusting the time of

acceleration/deceleration.