Delta Electronics AC Motor Drive VFD007S23A User Manual

Page 133

Advertising
background image

Chapter 5 Parameters|VFD-S Series

5-78

Revision August 2006, SE08, SW V2.61

the setting frequency of parameters, such as Max. operation frequency, 1

st

speed and etc.,

they are still needed to set with actual value.

P

A-02

I

A-03

A-01

+

+

+

+

Target
Value

Detection
Value
Gain

D

A-04

A-05

A-07

Integration's
Upper
Bound
Frequency

A-06

One-Time
Delay

Output Value

A-00

PID Frequency
Output
Command
Limit

Frequency
Command

If the input range of sensor is 0~SI_max, output range is SO_min~SO_max and then

Input

Per output

is

SI_max

SO_max-SO_min

, set drive input to sensor output

Set input range of drive is D_range= 10V(0~10V) or 16mA (4~20mA) that correspond to 0~1-00Hz

and then

Output

Per input

will be

1-00

D_range

According to the display value of F and H = actual value

¯A-13/1-00, and then

Display value of F, H

Actual value

=A-13/1-00. If you want the result to be display value = sensor output and actual value = drive output,

and then

A-13

1-00

SI_max

SO_max-SO_min

A-01

100

1-00

D_range

=

X

A-13 =

SI_max

SO_max-SO_min

A-01

100

X

D_range

X


Example:

Sensor: 0~6 psi input corresponds to 0~5V output drive AVI: 0~10V input corresponds to 0~60Hz, A-
01=100

A-13 =

6

5-0

100

100

X

10

X

= 12