Chapter 5 Parameters|VFD-S Series

5-60

Revision August 2006, SE08, SW V2.61

Following a power failure, the AC drive will start its speed search operation, only if the output

current is greater than the value determined by Pr.8-07. When the output current is less than

that of Pr.8-07, the AC drive output frequency is at a “speed synchronization point”. The drive

will start to accelerate or decelerate back to the operating frequency at which it was running

prior to the power failure.

Output
Frequency

Output
Voltage

08-06

08-05

08-04=d1

08-06

08-05

08-04=d2

Power
Input

Maximum Allowable
Power Loss Time

Baseblock Time

Speed Search

Speed
Synchronization
Detection

Maximum
Allowable Power

Baseblock Time

Speed search starts
with the Master
Frequency

Speed search starts with
Min. Output Frequency

8-08

Skip Frequency 1 Upper Limit

Unit: 0.1

8-09

Skip Frequency 1 Lower Limit

Unit: 0.1

8-10

Skip Frequency 2 Upper Limit

Unit: 0.1

8-11

Skip Frequency 2 Lower Limit

Unit: 0.1

8-12

Skip Frequency 3 Upper Limit

Unit: 0.1

8-13

Skip Frequency 3 Lower Limit

Unit: 0.1

Settings

d0.0 to d400Hz

Factory Setting: d0.0

These parameters determine Skip frequency. It will cause the AC drive to skip operation at

these frequency ranges with continuous frequency output.

Pr.8-9, Pr.8-11, Pr.8-13 are for Lower Bound setting, and the settings should follow as Pr.8-9

≧Pr.8-11≧Pr.8-13.

8-14

Auto Restart After Fault

Unit: 1

Settings

d0 to d10

Factory Setting: d0

After fault occurs (allowable faults: over-current OC, over-voltage OV), the AC drive can be

reset/restarted automatically up to 10 times. Setting this parameter to 0 will disable the

reset/restart operation after any fault has occurred. When enabled, the AC drive will restart

with speed search, which starts at the Master Frequency.