Delta Electronics AC Motor Drive VFD007S23A User Manual

Page 65

Advertising
background image

Chapter 5 Parameters|VFD-S Series

5-10

Revision August 2006, SE08, SW V2.61

Pr. Explanation

Settings

Factory

Setting

NOTE

9-00

Communication
Address

d1 to d254

d1

d0: Baud Rate 4800 bps

9-01 Transmission Speed

d1: Baud Rate 9600 bps

d1

9-01 Transmission Speed

d2: Baud Rate 19200 bps
d3: Baud Rate 38400 bps

d1

d0: Warn and Keep Operating

d1: Warn and Ramp to Stop
d2: Warn and Coast to Stop

9-02

Transmission Fault
Treatment

d3: Keep Operating without Warning

d0

d0: Disable

9-03 Time-out Detection

d1 to d20: time setting (1 sec

increment)

d0

d0: 7,N,2 (Modbus, ASCII)
d1: 7,E,1 (Modbus, ASCII)
d2: 7,O,1 (Modbus, ASCII)
d3: 8,N,2 (Modbus, ASCII)
d4: 8,E,1 (Modbus, ASCII)
d5: 8,O,1 (Modbus, ASCII)
d6: 8,N,2 (Modbus, RTU)
d7: 8,E,1 (Modbus, RTU)

9-04

Communication
Protocol

d8: 8,O,1 (Modbus, RTU)

d0

Group A PID Parameters

Pr. Explanation

Settings

Factory

Setting

NOTE

A-00

Input terminal for PID Feedback

d0: Disable PID function
d1: Negative PID feedback from

external terminal (AVI) 0 to
+10V

d2: Negative PID feedback from

external terminal (ACI) 4 to
20mA

d3: Positive PID feedback from

external terminal (AVI) 0 to
+10V

d4: Positive PID feedback from

external terminal (ACI) 4 to
20mA

d0

A-01

Gain over PID Detection value

d0 to d999

d100

A-02

Proportional Gain (P)

d0 to d999

d100

A-03

Integral Time (I)

d0 to d999

d100

A-04

Derivative Control (D)

d0 to d100

d0

A-05

Upper Bound for Integral Control

d0 to d100%

d100

A-06

Primary Delay Filter Time

d0 to d999

d0