Chapter 5 Parameters|VFD-S Series

Revision August 2006, SE08, SW V2.61

5-43

GND

B.B.(N.O.)

setting by d13

B.B.(N.C.)

setting by d14

Mx "Close": Operation available.

Mx "Open":Operation available.

NOTE

When a Base-Block signal is received, the AC drive will stop all output and the motor will free run.

When base block control is deactivated, the AC drive will start its speed search function and

synchronize with the motor speed, and then accelerate to Master Frequency.

External
base-block
signal

Output
frequency

Output
voltage

Speed search starts with the
reference value

Pr.8-06

Min. base-block time

Speed search operation

Pr.8-04=d1

Speed synchronization
detection


d15, d16 Increase/Decrease Master Frequency:

Parameter values d15, d16 program the Multi-Function Input Terminals: M1 (Pr.4-04), M2 (Pr.4-05),

M3 (Pr.4-06), M4 (Pr.4-07) or M5 (Pr.4-08) to incrementally increase/ decrease the Master

Frequency each time an input is received.

GND

setting by d15

setting by d16

Mx "Close": Freq. will increase
by one unit.

Mx "Close":Freq. will decrease
by one unit.

UP

DOWN


d17, d18 PLC Function Control:

Parameter value d17 programs Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3 (Pr.4-

06), M4 (Pr.4-07) or M5 (Pr.4-08) to enable the AC drive internal PLC program. Parameter value

d18 programs an input terminal to pause the PLC program.