Chapter 5 Parameters|VFD-S Series

Revision August 2006, SE08, SW V2.61

5-59

DC Braking during Start-up is used for loads that may move before AC drive starts, such as

fans and pumps. These loads may also be moving in the wrong direction. Under such

circumstances, DC Braking can be executed to hold the load in position before applying a

forward motion.

DC Braking during stopping is used to decrease stopping time and also to hold a stopped

load in position. For high inertial loads, a dynamic braking resistor may be needed for quick

decelerations.

8-04

Momentary Power Loss Operation Selection

Factory Setting: d0

Settings

d0

Operation stops after momentary power loss

d1

Operation continues after momentary power loss, speed search
starts with the Master Frequency reference value

d2

Operation continues after momentary power loss, speed search
starts with the minimum frequency

8-05

Maximum Allowable Power Loss Time

Unit: 0.1

Settings

d0.3 to d5.0Sec

Factory Setting: d2.0

During a power loss, if the power loss time is less than the time defined by this parameter, the

AC drive will resume operation. If the Maximum Allowable Power Loss Time is exceeded, the

AC drive output is then turned off.

8-06

Base Block Speed Search

Unit: 0.1

Settings

d0.3 to d5.0Sec

Factory Setting: d0.5

When a momentary power loss is detected, the AC drive turns off for a specified time interval

determined by Pr.8-06 before resuming operation. This time interval is called Base-Block.

This parameter should be set to a value where the residual output voltage is nearly zero,

before the drive resumes operation.

This parameter also determines the searching time when performing external Base-Block and

fault reset.

8-07

Current Limit for Speed Search

Unit: 1

Settings

d30 to d200

Factory Setting: d150