Chapter 5 Parameters|VFD-S Series

Revision August 2006, SE08, SW V2.61

5-51

1

2

3

4

5

6

7

Weights

Bit

0=Forward

1=Reverse

Direction of 1st

Pr.5-00 =FWD

speed for

Direction of 2nd

Pr.5-01 =REV

speed for

Direction of 3rd

Pr.5-02 = F

speed for

Direction of 4th

Pr.5-03 = F

speed for

Direction of 5

Pr.5-04 = F

th speed for

Direction of 6

Pr.5-05 = REV

th speed for

Direction of 7

Pr.5-06 = F

th speed for

0

0

1

0

0

1

1

0

0

Direction

WD

WD

WD

WD

WD

The setting value = bit7 x 2

7

+bit6 x 2

6

+bit5 x 2

5

+bit4 x 2

4

+bit3 x 2

3

+bit2 x 2

2

+bit1 x 2

1

+bit0 x 2

0

= 0 x 2

7

+1 x 2

6

+0 x 2

5

+0 x 2

4

+0 x 2

3

+1 x 2

2

+0 x 2

1

+0 x 2

0

= 0+64+0+0+0+4+0+0
= 68

Setting Pr.5-08 as d68.

5-09

Time Duration of Zero Step Speed

Unit: 1

5-10

Time Duration of 1st Step Speed

Unit: 1

5-11

Time Duration of 2nd Step Speed

Unit: 1

5-12

Time Duration of 3rd Step Speed

Unit: 1

5-13

Time Duration of 4th Step Speed

Unit: 1

5-14

Time Duration of 5th Step Speed

Unit: 1

5-15

Time Duration of 6th Step Speed

Unit: 1

5-16

Time Duration of 7th Step Speed

Unit: 1

Settings

d0 to d65500

Factory Setting: d0

Pr.5-10 to Pr.5-16 correspond to operation time of each multi-step speed defined by

parameters 5-00 to 5-06. The maximum value of these parameters is 65500 sec., and it’s

displayed as d65.5.

NOTE

If a parameter is set to “d0” (0 Sec), the corresponding step will be skipped. This is commonly used

to reduce number of program steps.