Chapter 5 Parameters|VFD-S Series

5-76

Revision August 2006, SE08, SW V2.61

When this parameter is set to gain =1, PID output is Derivative time. At this time, error value –

error value of the preceding item= additional respond speed and it is easy to have over

compensation situation.

A-05

Upper Bound for Integral Control

Unit: 1

Settings

d0 to d100%

Factory Setting: d100

This parameter determines the Upper Bound for Integral Control while operating in the PID

feedback loop. (Limit = 1-00

×A-05 %). During a fast Integration response, it is possible for

the frequency to spike beyond a reasonable point. This parameter will limit this frequency

spike.

A-06

Primary Delay Filter Time

Unit: 2 msec

Settings

d0 to d999

Factory Setting: d0

Primary Delay Filter Time will slow down oscillation of the system.

A setting of d0 disables this function.

A-07

PID Output Frequency Limit

Unit: 1

Settings

d0 to d110%

Factory Setting: d100

This parameter determines the limit of the PID output frequency. If this parameter is set to

110%, then the maximum output frequency while in the PID operation will be (110% x Pr.01-

00) 66Hz.

A-08

Feedback Signal Detection Time

Unit: 0.1

Settings

d0.0 to d650 seconds

Factory Setting: d0.0

This parameter defines the detection time for the loss of a feedback analog signal. The drive

will follow the operating procedure programmed in Pr.A-09 if the feedback signal is lost for

more than the time set in Pr. A-08.

A setting of 0.0 disables this function.

A-09

Treatment of the Erroneous Feedback Signals

Factory Setting: d0

Settings

d0

Warning and RAMP to stop

d1

Warning and COAST to stop