Chapter 5 Parameters|VFD-S Series

Revision August 2006, SE08, SW V2.61

5-33

Preliminary Counter Value Attained Output

(Pr. 3-04=d3)
(Pr. 3-05 to Pr. 3-06=d15)

Terminal Count Value Attained Output

(Pr.3-03=d5)
(Pr.3-05 to Pr.3-06=d14)

Display
(Pr.0-04=d1)

TRG

Counter Trigger Signal
Multi-function Input Terminal

The width of trigger signal
should not be less than
2ms(<250 Hz)

2ms

2ms

3-05

Multi-function Output Terminal 1 (Photocoupler output)

Factory Setting: d1

3-06

Multi-function Output Terminal 2 (relay output)

Factory Setting: d8

Settings d0 to d18

Setting

Function

Description

d0 No

Function

d1

AC Drive Operational

the output terminal will be activated when the drive is

running.

d2

Master Frequency Attained the output will be activated when the AC drive attains

Maximum Output Frequency.

d3

Zero Speed

the output will be activated when Command Frequency

is lower than the Minimum Output Frequency.

d4

Over Torque Detection

the output will be activated as long as the over-torque is

detected. Pr.6-04 determines the Over-Torque detection

level.

d5

Base-Block (B.B.) Indication the output will be activated when the output of the AC

drive is shut off by external Baseblock.

d6

Low-Voltage Indication

the output will be activated when low voltage is detected.

d7

Operation Mode Indication

the output will be activated when the operation of the AC

drive is controlled by External Control Terminals.

d8

Fault Indication

the output will be activated when faults occur (oc, ov,

oH, oL, oL1, EF, cF3, HPF, ocA, ocd, ocn, GF).

d9

Desired Frequency Attained the output will be activated when the desired frequency

(Pr.3-02)is attained.