Fronius Energy Package User Manual

Page 112

Advertising
background image

110

The inverter disconnects automatically from the grid, the grid is then monitored as specified
and the inverter attempts to resume feeding energy into the grid.

*) If the status code is displayed all the time: Notify a Fronius-trained service engineer.

**) Fault is rectified automatically. If this status code keeps recurring, contact your system
engineer.

Status codes –
Class 4

Some of the class 4 status codes necessitate intervention by a Fronius-trained service en-
gineer.

Code

Description

Behaviour

Remedy

301

Overcurrent (AC)

Short-term interruption while
feeding energy into the grid.
The inverter repeats its start-
up routine.

*)

302

Overcurrent (DC)

303

DC module overtemperature (PV)

Short-term interruption while
feeding energy into the grid.
The inverter repeats its startup
routine.

Purge cooling air open-
ings and heat sink; **)

304

AC module overtemperature

305

No power being fed in, despite closed
relays

Short-term interruption while
feeding energy into the grid.
The inverter repeats its startup
routine.

**)

306

There is not enough PV power avail-
able for feeding energy into the grid
and no power has been requested
from the battery.

Short-term interruption while
feeding energy into the grid.
The inverter repeats its startup
routine.

Wait for sufficient insola-
tion; wait for an energy
management command;
**)

307

DC low
DC input voltage too low for feeding
energy into the grid

Short-term interruption while
feeding energy into the grid.
The inverter repeats its startup
routine.

Wait for sufficient insola-
tion;
**)

IMPORTANT! Due to the low level of insolation early in the morning and in the evening, the status codes 306
(Power low) and 307 (DC low) are displayed routinely at these times of day. These status codes do not indicate
any kind of fault.
308

Intermediate circuit voltage too high

Short-term interruption while
feeding energy into the grid.
The inverter repeats its startup
routine.

**)

309

PV input voltage too high

313

Battery input voltage too high.

Short-term interruption while
feeding energy into the grid.
The inverter repeats its startup
routine. This service code may
occur sporadically even though
there is no actual fault.

Switch on, connect or
check battery;
*)

314,
315

Internal system error

Short-term interruption while
feeding energy into the grid.
The inverter repeats its startup
routine.

*)

324

DC module overtemperature (battery)

Short-term interruption while
feeding energy into the grid.
The inverter repeats its startup
routine.

Purge cooling air open-
ings and heat sink; **)

Advertising