Fronius Energy Package User Manual

Page 49

Advertising
background image

47

EN

Version

Displays the version and serial numbers of the PC boards in the inverter (e.g. for service
purposes)

Grid monitoring:

GMTi
Start-up time of inverter in s

GMTr
Reconnection time in s following a grid fault

ULL
Mean grid voltage over 10 minutes in V

LLTrip
Trip time for long-term voltage monitoring

Grid voltage limits:

UILmax
Upper inner grid voltage in V

UILmin
Lower inner grid voltage in V

Grid frequency limits:

FILmax
Upper inner grid frequency in Hz

FILmin
Lower inner grid frequency in Hz

Q-mode:

Current cos phi power factor setting
(e.g. Constant Cos(phi) / Constant Q / Q(U) characteristic / etc.)

AC power limit:

Max. P AC
Manual power reduction

AC voltage derating:

Status
ON / OFF – Voltage-dependent power reduction

GVDPRe
Threshold at which the voltage-dependent power reduction be-
gins

GVDPRv
Reduction gradient used to reduce the power, e.g.: 10% per volt
above the GVDPRe threshold

Message
Activates the sending of an info message via Fronius Solar Net

Fault Ride Through:

Status – default setting: OFF
If the function is activated, the inverter does not switch off im-
mediately in the event of a short-term AC voltage dip (outside of
the limits specified by the grid supplier), but instead continues
to feed in power for a defined period.

DB min – Default setting: 90%
“Dead Band Minimum” setting in per cent

DB max – Default setting: 120%
“Dead Band Maximum” setting in per cent

k-Fac. – Default setting: 0

Advertising