When choosing the switch-on point, the weather conditions and anticipated insolation
should also be taken into account.

Application example
Switch-on point = 2000 W, switch-off point = 1800 W

If the inverter is outputting 2000 W or above, then the floating switch contact on the inverter
is switched on.
If the inverter output falls to below 1800 W, the floating switch contact is switched off.

Possible applications:
Operating a heat pump or an air-conditioning system using as much self-generated power
as possible

Time / Date

Set the time, date and automatic changeover between summer and winter time

Set time
Set the time (hh:mm:ss or hh:mm am/pm – depending on the setting for the time display
format)

Set date
Set the date (dd.mm.yyyy or mm/dd/yyyy - depending on the setting for the date display
format)

Summer/winter time
Activate/deactivate automatic changeover between summer and winter time

IMPORTANT! The time and date must be set accurately in order for the day and year val-
ues and for the day characteristic to be displayed correctly.

Display settings

Language
Set language for display

Setting range

Set time / Set date / Time display format / Date display format /
Summer/winter time

Time display format
For specifying the time display format

Setting range

12hrs / 24hrs

Factory setting

Depends on country setup

Date display format
For specifying the date display format

Setting range

mm/dd/yyyy / dd.mm.yy

Factory setting

Depends on country setup

Setting range

on / off

Factory setting

on

Setting range

Language / Night mode / Contrast / Illumination