Fronius Energy Package User Manual

Page 115

Advertising
background image

113

EN

*) If the status code is displayed all the time: Notify a Fronius-trained service engineer.

Code

Description

Behaviour

Remedy

502

Insulation fault on solar mod-
ules or on Fronius Solar Bat-
tery

Warning message is
shown on the display

**)

509

No energy fed into the grid in
the past 24 hours

Warning message is
shown on the display

Acknowledge status code;
check whether all the conditions for
the problem-free feeding of energy
into the grid have been met (e.g. are
the solar modules covered with
snow?); **)

515

Unable to communicate with
filter

Warning message on
the display

*)

516

Unable to communicate with
the data storage unit

Data storage unit warn-
ing message

*)

517

Power derating caused by ex-
cessively high temperatures

When power derating
occurs, a warning mes-
sage is shown on the
display.

If necessary, purge cooling air open-
ings and heat sink;
fault is rectified automatically; **)

519

Unable to communicate with
the data storage unit

Data storage unit warn-
ing message

*)

520

No energy fed into the grid by
the PV in the past 24 hours

Warning message is
shown on the display

Acknowledge status code;
check whether all the conditions for
the problem-free feeding of energy
into the grid have been met (e.g. are
the solar modules covered with
snow?); *)

522

DC low (PV). No PV voltage
available.

Warning message on
the display

In the case of hybrid systems, this
message appears overnight or if no
photovoltaics are connected to the
Fronius Symo Hybrid; *)

523

DC low (battery). The battery
has been activated but is either
not connected or is not
switched on.

Warning message on
the display

Switch on, connect or check battery;
*)

558,
559

Functional incompatibility (one
or more PC boards in the in-
verter are not compatible with
each other, e.g. after a PC
board has been replaced)

Warning message on
the display

Update inverter firmware; *)

560

Power derating caused by
overfrequency

Displayed when grid fre-
quency becomes exces-
sively high. The power is
reduced.

As soon as the grid frequency is back
within the permissible range and the
inverter has returned to normal oper-
ation, the fault is rectified automati-
cally; **)

567

Power derating caused by
overvoltage

Displayed when grid
voltage becomes exces-
sively high. The power is
reduced.

As soon as the grid voltage is back
within the permissible range and the
inverter has returned to normal oper-
ation, the fault is rectified automati-
cally; **)

573

Power derating caused by ex-
cessively low temperatures

When power derating
occurs, a warning mes-
sage is shown on the
display.

Fault rectified automatically; **)