Fronius Energy Package User Manual

Page 113

Advertising
background image

111

EN

Code

Description

Behaviour

Remedy

401

Unable to communicate with the power
stage set

The inverter will automati-
cally attempt to connect
again and, if possible, will
resume feeding energy into
the grid.

*)

406

DC module temperature sensor faulty
(PV)

407

AC module temperature sensor faulty

408

DC component measured in the grid too
high

412

Fixed voltage mode has been selected
instead of MPP voltage mode, and the
fixed voltage has been set to too low or
too high a value.

-

**)

415

Safety cut-out via option card or RECER-
BO has triggered

The inverter is not feeding
any energy into the grid.

*)

416

No communication possible between
power stage set and control system.

The inverter will automati-
cally attempt to connect
again and, if possible, will
resume feeding energy into
the grid.

*)

417

Hardware ID problem

The inverter will automati-
cally attempt to connect
again and, if possible, will
resume feeding energy into
the grid.

Update inverter firm-
ware; *)

420

Unable to communicate with system
monitoring

425

Unable to communicate with the power
stage set

426 -
427

Possible hardware fault

431,
432

Software problem

The inverter is not feeding
any energy into the grid.

Perform AC reset
(switch automatic circuit
breaker off and on
again); update inverter
firmware; *)

436

Functional incompatibility (one or more
PC boards in the inverter are not com-
patible with each other, e.g. after a PC
board has been replaced)

The inverter will automati-
cally attempt to connect
again and, if possible, will
resume feeding energy into
the grid.

Update inverter firm-
ware; *)

437

Power stage set problem

438

Functional incompatibility (one or more
PC boards in the inverter are not com-
patible with each other, e.g. after a PC
board has been replaced)

The inverter will automati-
cally attempt to connect
again and, if possible, will
resume feeding energy into
the grid.

Update inverter firm-
ware; *)

445

-

Compatibility error (e.g. due to re-
placement of a PC board)

-

Invalid power stage set configura-
tion

The inverter is not feeding
any energy into the grid.

Update inverter firm-
ware; *)

447

Insulation fault (PV or battery)

The inverter is not feeding
any energy into the grid.

*)

450

Guard cannot be found