Load manage-
ment

(1)

Status

(2)

Controlling
- Control via Energy Manager deactivated.
- Control via Energy Manager is based on the power produced.
- Control via Energy Manager is based on surplus power (with feed-in limits). This
option can only be selected if a meter has been connected. Control via Energy
Manger is based on the amount of energy actually fed into the grid.

(3)

Thresholds
- on: For entering an effective power limit as of which output I/O 1 is to be activated.

Example involving Fronius Energy Package without photovoltaics but with a sec-
ond producer within the home
Second producer on home network:

2000 W

Household consumption:

500 W

Target value set at feed-in point:

0 W

Energy fed into Fronius Solar Battery:

1500 W

Power consumed (AC) by inverter:

1500 W

Energy fed into the public grid:

0 W

Example involving Fronius Energy Package plus a second producer within the
home (with AC max. limiting)
PV system connected to Fronius Symo Hybrid:

1000 W

Second producer on home network:

2000 W

Household consumption:

500 W

Target value set at feed-in point:

0 W

Max. AC power consumption limited to:

1000 W

Energy fed into Fronius Solar Battery:

2000 W

Power consumed (AC) by inverter:

1000 W

Energy fed into the public grid:

500 W