Redback Wallmount Dimmer

Installation

Operator Manual V1.3

Page 9

2.6.3 Connecting the Load Circuits

Models with internally connected load circuits are provided with numbered 6mm terminals
for Active (A) and Neutral (N) for each load circuit. One 16mm Earth (E) terminal is
provided for every 6 load connections. These connections are wired directly to the outlets at
the required locations in the building.


Models with front mounted outlets have numbers indicating their channel.

Australian Outlets

GST Outlets


Redbacks fitted with GST outlets have 2 DIMMING (or optionally switched) outlets and one
HOT POWER outlet per channel. The dimming and hot power outlets of each channel are all
connected to the channels load circuit breaker. The total load per channel must not exceed
10 amps.

2.6.4 Connecting DMX512

DMX 512 is the industry standard for the transmission of digital control signals between
lighting equipment. DMX is usually “looped” from one piece of equipment to the next.
See “DMX Explained and Typical Installations” for more information.

DMX 512 is connected to the Redback Wallmount dimmer by using the screw terminals
inside the unit. The DMX512 connection is high impedance. This allows the DMX512 to be
wired in parallel to other dimmers. If the DMX line ends at this dimmer (is not looped to
other dimmers or devices) then the DMX TERM switch must be set to TERM.

Earths for

Channels 1 to 6

Earths for

Channels 7 to 12

Channel 1 Active

Channel 1 Neutral