Altitude, Cleanness, Cooling system – H3C Technologies H3C SR6600 User Manual

Page 13

Advertising
background image

3

Altitude

Table 3 Altitude requirements

Item Altitude

Operating altitude

–60 m (–196.85 ft) to 4 km (2.49 miles)

Storage altitude

–60 m (–196.85 ft) to 4.5 km (2.8 miles)

Cleanness

Dust buildup on the chassis might result in electrostatic adsorption, which causes poor contact of metal

components and contact points, especially when indoor relative humidity is low. In the worst case,
electrostatic adsorption can cause communication failure.

Table 4 Dust concentration limit in the equipment room

Substance

Concentration limit (particles/m

3

)

Dust particles

≤ 3 x 10

4

(No visible dust on desk in three days)

NOTE:

Dust particle diameter ≥ 5 μm

The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion and
premature aging of components, as shown in

Table 5

.

Table 5 Harmful gas limits in an equipment room

Gas Max.

(mg/m

3

)

SO

2

0.2

H

2

S 0.006

NH

3

0.05

Cl

2

0.01

Cooling system

The H3C SR6604 and SR6608 routers adopt left to right airflow for heat dissipation.