Rs485 2-wire networks – Yaskawa F7 Modbus User Manual

Page 10

Advertising
background image

Connections 1-5

RS485 2-Wire Networks

RS485 2-wire networks can be either single or multi-drop networks, with each slave device on the network assigned a unique node address. A

maximum of 31 devices may reside on any network segment before a repeater is required. Terminating resistors must be installed on the first

and last devices on each network segment. The maximum segment length is 4000ft (1200m). All RS485 communications are half-duplex










Figure 1.5 – RS485 2–Wire Network Connection