Troubleshooting Serial COM 3-3

3.3:

Verify that the contents of the message adheres to the protocol format as described previously.

3.3.1: Verify that the node address is valid.

3.3.2: Verify that the function code is valid

3.3.3: Verify that the register address is valid

3.3.4: Verify that the number of data bytes is correct is valid

3.3.5: Verify that the CRC is correctly calculated.

3.3.6: Verify that the message requires a response.

4:

Verify the contents of the response message.

4.1:

Connect an oscilloscope between the controller RxD and GND.

4.1.1: Verify that the message pulse train exists and contains the correct number of pulses. Refer to the chapter

Message Formats for information on the message contents.

4.1.2: Verify that he signal levels adhere to the RS232 standard.

4.2:

Capture the response message sent by the controller in a hexadecimal format and record it below.

[

] [

] [

] [

] [

] [

] [

] [

] [

] [

]

[

] [

] [

] [

] [

] [

] [

] [

] [

] [

]

[

] [

] [

] [

] [

] [

] [

] [

] [

] [

]

[

] [

] [

] [

] [

] [

] [

] [

] [

] [

]

4.3:

Verify that the contents of the message adheres to the protocol format as described previously.

4.3.1: Verify that the node address is valid.

4.3.2: Verify that the function code is valid

4.3.4: Verify that the number of data bytes is correct is valid

4.3.3: Verify that the register address is valid

4.3.4: Verify that the CRC is correctly calculated.