Communications parameters, Communications parameters -6, Rs232 communications – Yaskawa F7 Modbus User Manual

Page 11: Connections 1-6

Advertising
background image

Connections 1-6

Communications Parameters

These communications parameters affect serial communications through RS232, RS422 and RS485. The RS232 communications parameters

cannot be changed. Also, the node address is ignored when communicating via RS232.
All serial communications parameters can only be changed via the operator keypad.

RS232 Communications

The RS232 communications’ parameters are fixed at the values shown below. Although the node address is ignored, a node address of 1 is

typically used by the master when communicating to the F7 drive in this method.

Table 1.1 – RS232 (RJ45 port) Communications’ Parameters

Value

Description

Baud rate

9600

Parity None
Stop Bits

1

Node Address

N/A

RS422/RS485 Communications

Node Address – H5-01

The node address is set through F7 drive parameter H5-01. When communicating via RS422 or RS485, a unique node address between 0

and 20h (32 dec), inclusive, must be entered. The default F7 drive address is 1Fh (31 dec). The address is always entered as a hexadecimal

number (refer to the conversion chart in Chapter 4). Address 0 is typically reserved for global messages.

Baud rate – H5-02

Select the baud rate that matches the controller’s serial configuration. The default baud rate is 9600 (3).

Table 1.2 – Baud Rate – Parameter H5-02

Value

Description

0 1200
1 2400
2 4800
3 9600
4 19200

Parity – H5-03

Select the parity that matches the controller’s serial configuration. The default parity is None (0).

Table 1.3 – Parity – Parameter H5-03

Value

Description

0 None
1 Even
2 Odd

Serial Fault Select – H5-04

Select the drive operation method when a serial fault (CE) is declared. The default method is Alarm Only (3).

Table 1.4 – Serial Fault Select – Parameter H5-04

Value

Description

0

Ramp to Stop (Fault)

1

Coast to Stop (Fault)

2 Fast

Stop

(Fault)

3

Alarm Only (Alarm)

4

Run at d1-04 frequency

Advertising