Warnings and Cautions

This Section provides warnings and cautions pertinent to this product, that if
not heeded, may result in personal injury, fatality, or equipment damage.
Yaskawa is not responsible for consequences of ignoring these instructions.

WARNING

YASKAWA manufactures component parts that can be used in a wide variety of industrial applications. The selection and application of

YASKAWA products remains the responsibility of the equipment designer or end user. YASKAWA accepts no responsibility for the way its

products are incorporated into the final system design. Under no circumstances should any YASKAWA product be incorporated into any product

or design as the exclusive or sole safety control. Without exception, all controls should be designed to detect faults dynamically and to fail safely

under all circumstances. All products designed to incorporate a component part manufactured by YASKAWA must be supplied to the end user

with appropriate warnings and instructions as to that part’s safe use and operation. Any warnings provided by YASKAWA must be promptly

provided to the end user. YASKAWA offers an express warranty only as to the quality of its products in conforming to standards and

specifications published in the YASKAWA manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED. YASKAWA assumes

no liability for any personal injury, property damage, losses, or claims arising from misapplication of its products.

WARNING

Read and understand this manual before installing, operating, or servicing this F7 drive. All warnings, cautions, and instructions must be

followed. All activity must be performed by qualified personnel. The F7 drive must be installed according to this manual and local codes.

Do not connect or disconnect wiring while the power is on. Do not remove covers or touch circuit boards while the power is on. Do not

remove or insert the digital operator while power is on.

Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off.

Status indicator LEDs and Digital Operator display will be extinguished when the DC bus voltage is below 50 VDC. To prevent electric

shock, wait at least 5 minutes after all indicators are OFF and measure DC bus voltage and verify that it is at a safe level.

Do not perform a withstand voltage test on any part of the unit. This equipment uses sensitive devices and may be damaged by high

voltage.

The F7 drive is not suitable for circuits capable of delivering more than the specified RMS symmetrical amperes. Install adequate branch

short circuit protection per applicable codes. Refer to the specification. Failure to do so may result in equipment damage and/or personal

injury.

Do not connect unapproved LC or RC interference suppression filters, capacitors, or over voltage protection devices to the output of the F7

drive. Capacitors may generate peak currents that exceed F7 drive specifications.

To avoid unnecessary fault displays, caused by contactors or output switches placed between F7 drive and motor, auxiliary contacts must be

properly integrated into the control logic circuit.

YASKAWA is not responsible for any modification of the product made by the user, doing so will void the warranty. This product must not

be modified.

Verify that the rated voltage of the F7 drive matches the voltage of the incoming power supply before applying power.

To meet CE directives, proper line filters and proper installation are required.

Some drawings in this manual may be shown with protective covers or shields removed, to describe details. These must be replaced before

operation.

Observe Electrostatic Discharge Procedures when handling the F7 drive and F7 drive components to prevent ESD damage.

The attached equipment may start unexpectedly upon application of power to the F7 drive. Clear all personnel from the F7 drive, motor and

machine area prior to applying power. Secure covers, couplings, shaft keys, machine beds and all safety equipment before energizing the

F7 drive.

Do not attempt to disassemble this unit. There are no user serviceable parts. Disassembling this unit will void any and all

warranties.