F7u parameters 4-21 – Yaskawa F7 Modbus User Manual

Page 60

Advertising
background image

F7U Parameters 4-21

Table 4.12 – L Parameters

Mode

Name

Addr

Digital Operator

Text

Data

Parameter Range or

Data Description

Inc

Default

Run

V/f

V/f

wPG

OLV

FV

Dep

L5-01

049Eh

Num of Restarts

0 ~ 10

1

0

A

A

A

A

0

No Flt Relay

L5-02 049Fh

Restart

Sel

1

Flt Relay Active

1

0

A A A A

0 Disabled
1 OL@SpdAgree-Alm
2

OL At RUN - Alm

3 OL@SpdAgree-Flt
4

OL At RUN - Flt

5 UL@SpdAgree-Alm
6

UL At RUN - Alm

7 UL@SpdAgree-Flt

L6-01

04A1h

Torq Det 1 Sel

8

UL At RUN - Flt

1

0

A A A A

L6-02

04A2h

Torq Det 1 Lvl

0 ~ 300 %

1 %

150 %

A

A

A

A

L6-03

04A3h

Torq Det 1 Time

0.0 ~ 10.0 Sec

0.1 Sec

0.1 Sec

A

A

A

A

0 Disabled
1 OL@SpdAgree-Alm
2

OL At RUN - Alm

3 OL@SpdAgree-Flt
4

OL At RUN - Flt

5 UL@SpdAgree-Alm
6

UL At RUN - Alm

7 UL@SpdAgree-Flt

L6-04

04A4h

Torq Det 2 Sel

8

UL At RUN - Flt

1

0

A A A A

L6-05

04A5h

Torq Det 2 Lvl

0 ~ 300 %

1 %

150 %

A

A

A

A

L6-06

04A6h

Torq Det 2 Time

0.0 ~ 10.0 Sec

0.1 Sec

0.1 Sec

A

A

A

A

L7-01

04A7h

Torq Limit Fwd

0 ~ 300 %

1 %

200 %

NA

NA

A

A

L7-02

04A8h

Torq Limit Rev

0 ~ 300 %

1 %

200 %

NA

NA

A

A

L7-03

04A9h

Torq Lmt Fwd Rgn

0 ~ 300 %

1 %

200 %

NA

NA

A

A

L7-04

04AAh

Torq Lmt Rev Rgn

0 ~ 300 %

1 %

200 %

NA

NA

A

A

L7-06

04ACh

Torq Limit Time

5 ~ 10000 ms

1 ms

200 ms

NA

NA

A

NA

0

60 Hz VT2

L7-07

04C9h

Torque Limit Sel

1

50 Hz HST1

1 0

NA

NA

A

NA

0 Not

Provided

L8-01

04ADh

DB Resistor Prot

1 Provided

1

0

A A A A

L8-02

04AEh

OH Pre-Alarm Lvl

50 ~ 130 Deg

1 ºC

95 ºC

A

A

A

A

0

Ramp to Stop

1

Coast to Stop

2 Fast-Stop

L8-03

04AFh

OH Pre-Alarm Sel

3 Alarm

Only

1

3

A A A A

0 Disabled

L8-05

04B1h

Ph Loss In Sel

1 Enabled

1

0

A A A A

0 Memobus(Modbus)
1

N2 (Metasys)

L8-07

04B3h

Ph Loss Out Sel

2 FLN

(APOGEE)

1

0

A A A A

0 Disabled

L8-09

04B5h

Ground Fault Sel

1 Enabled

1

1

A A A A

0

Fan On-Run Mode

L8-10

04B6h

Fan On/Off Sel

1

Fan Always On

1

0

A A A A

0 Disabled

L8-11

04B7h

Fan Delay Time

1 Enabled

1

Sec

60

Sec

A A A A

L8-12

04B8h

Ambient Temp

45 ~ 60 Deg

1 ºC

45 ºC

A

A

A

A

0 Disabled
1 Enabled

L8-15

04BBh

OL2 Sel @ L-Spd

1 Enabled

1

1

A A A A

0 Disabled

L8-18

04BEh

Soft CLA Sel

1 Enabled

1

1

A A A A

Advertising