E parameters, F7u parameters 4-12 – Yaskawa F7 Modbus User Manual

Page 51

Advertising
background image

F7U Parameters 4-12

Table 4.8 – D Parameters

Mode

Name

Addr

Digital Operator

Text

Data

Parameter Range or

Data Description

Inc

Default

Run

V/f

V/f

wPG

OLV

FV

Dep

d6-06

02A5h

FieldForce Limit

100 ~ 400 %

1 %

400 %

NA

NA

A

A

E Parameters

Table 4.9 – E Parameters

Mode

Name

Addr

Digital Operator

Text

Data

Parameter Range or

Data Description

Inc

Default

Run

V/f

V/f

wPG

OLV

FV

Dep

E1-01

0300h

Input Voltage

155 ~ 255 VAC

1 VAC

200 VAC

Q

Q

Q

Q

A1-02

0h 50

Hz

1h

60 Hz Saturation

2h

50 Hz Saturation

3h 72

Hz

4h

50 Hz VT1

5h

50 Hz VT2

6h

60 Hz VT1

7h

60 Hz VT2

8h

50 Hz HST1

9h

50 Hz HST2

Ah

60 Hz HST1

Bh

60 Hz HST2

Ch 90

Hz

Dh 120

Hz

Eh 180

Hz

Fh Custom

V/F

E1-03 0302h

V/F

Selection

FFh

Custom w/o limit

1 0fh

Q

Q

NA

NA

A1-03

A1-02

E1-04

0303h

Max Frequency

40.0 ~ 400.0 Hz

0.1 Hz

60.0 Hz

Q

Q

Q

Q

A1-02

E1-05

0304h

Max Voltage

0.0 ~ 255.0 VAC

0.1 VAC

230.0 VAC

Q

Q

Q

Q

A1-02

E1-06

0305h

Base Frequency

0.0 ~ 400.0 Hz

0.1 Hz

60.0 Hz

Q

Q

Q

Q

A1-02

E1-07

0306h

Mid Frequency A

0.0 ~ 400.0 Hz

0.1 Hz

3.0 Hz

A

A

A

NA

A1-02

E1-08

0307h

Mid Voltage A

0.0 ~ 255.0 VAC

0.1 VAC

13.0 VAC

A

A

A

NA

A1-02

E1-09

0308h

Min Frequency

0.0 ~ 400.0 Hz

0.1 Hz

1.5 Hz

Q

Q

Q

A

A1-02

E1-10

0309h

Min Voltage

0.0 ~ 255.0 VAC

0.1 VAC

9.0 VAC

A

A

A

NA

A1-02

E1-11

030Ah

Mid Frequency B

0.0 ~ 400.0 Hz

0.1 Hz

0.0 Hz

A

A

A

A

A1-02

E1-12

030Bh

Mid Voltage B

0.0 ~ 255.0 VAC

0.1 VAC

0.0 VAC

A

A

A

A

A1-02

E1-13

030Ch

Base Voltage

0.0 ~ 255.0 VAC

0.1 VAC

230.0 VAC

A

A

Q

Q

A1-02

E2-01

030Eh

Motor Rated FLA

0.1 ~ 1500.0 A

0.1 A

14.0 A

Q

Q

Q

Q

o2-04

E2-02

030Fh

Motor Rated Slip

0.0 ~ 20.0 Hz

0.01 Hz

3.3 Hz

A

A

A

A

E2-03

0310h

No-Load Current

0.0 ~ 1500.0 A

0.1 A

4.5 A

A

A

A

A

o2-04

E2-04

0311h

Number of Poles

2 ~ 48

1

4

NA

Q

NA

Q

E2-05

0312h

Term Resistance

0.0 ~ 65.0 Ohm

0.1 Ohm

0.771 Ohm

A

A

A

A

E2-06

0313h

Leak Inductance

0.0 ~ 40.0 %

0.1 %

19.60 %

NA

NA

A

A

E2-07

0314h

Saturation Comp1

0.0 ~ 0.5

0.01

0

NA

NA

A

A

E2-08

0315h

Saturation Comp2

0.0 ~ 0.75

0.01

0

NA

NA

A

A

E2-09

0316h

Mechanical Loss

0.0 ~ 10.0 %

0.1 %

0.00 %

NA

NA

A

A

E2-10

0317h

Tcomp Iron Loss

0 ~ 65535 W

1 W

0 W

A

A

NA

NA

E2-11

0318h

Mtr Rated Power

0.0 ~ 650.0 kW

0.01 kW

0.4 kW

Q

Q

Q

Q

E2-12

0328h

Saturation Comp3

1.3 ~ 1.6

0.01

1.3

NA

NA

A

A

0 V/f
1

V/f w/ PG

2

Open Loop Vector(OLV)

E3-01 0319h Control

Method

3

Flux Vector (FV)

1

2

A A A A

E3-02

031Ah

Max Frequency

40.0 ~ 400.0 Hz

0.1 Hz

60.0 Hz

A

A

A

A

E3-03

031Bh

Max Voltage

0.0 ~ 255.0 VAC

0.1 VAC

230.0 VAC

A

A

A

A

E3-01

E3-04

031Ch

Base Frequency

0.0 ~ 400.0 Hz

0.1 Hz

60.0 Hz

A

A

A

A

E3-05

031Dh

Mid Frequency

0.0 ~ 400.0 Hz

0.1 Hz

3.0 Hz

A

A

A

NA

E3-06

031Eh

Mid Voltage

0.0 ~ 255.0 VAC

0.1 VAC

10.0 VAC

A

A

A

NA

E3-01

E3-07

031Fh

Min Frequency

0.0 ~ 400.0 Hz

0.1 Hz

0.5 Hz

A

A

A

A

E3-08

0320h

Min Voltage

0.0 ~ 255.0 VAC

0.1 VAC

1.7 VAC

A

A

A

NA

E3-01

E4-01

0321h

Motor Rated FLA

0.0 ~ 1500.0 A

0.1 A

0.0 A

A

A

A

A

o2-04

E4-02

0322h

Motor Rated Slip

0.0 ~ 20.0 Hz

0.01 Hz

0.0 Hz

A

A

A

A

E4-03

0323h

No-Load Current

0.0 ~ 1500.0 A

0.1 A

0.0 A

A

A

A

A

o2-04

E4-04

0324h

Number of Poles

2 ~ 48

1

4

NA

A

NA

A

E4-05

0325h

Term Resistance

0.0 ~ 65.0 Ohm

0.1 Ohm

0.0 Ohm

A

A

A

A

E4-06

0326h

Leak Inductance

0.0 ~ 40.0 %

0.1 %

0.00 %

NA

NA

A

A

E4-07

0327h

Mtr Rated Power

0.0 ~ 650.0 kW

0.01 kW

0.4 kW

A

A

A

A

Advertising