Message Formats 2-6

Loop-Back Test – Function Code 08H

The Loop-Back Test is used to verify that the communications parameters for the F7 drive have been set correctly and that the connection is

correct. The message should be constructed exactly as shown below. If everything is set and connected correctly, the received response will

match the response shown below.

Loop-Back Test - 08h

The Loop-Back test function (08h) is used for checking signal transmission between master and slaves. The command message format is shown

below.

Table 2.8 - Loop-Back Command Message

Description

Data

Slave Address

01h

Function Code

08h

Upper

00h

Test Code

Lower

00h

Upper

A5h

Data

Lower

37h

Upper

DAh

CRC-16

Lower

8Dh

Each F7 drive slave address is set via. parameter H5-01. Valid slave addresses must be in the range of 1 to 20 hex (1 to 32 dec) and entered as a

hexadecimal number. No two slaves may have the same address. The master addresses the slave by placing the slave address in the slave address

field of the message. In the command message above, the slave is addressed at 01h. Broadcast address 0 is not valid for Loop-Back test

commands.
The function code of this message is 08h (Loop-Back test).
The test code must be set to 0000h. This function specifies that the data passed in the command message is to be returned (looped back) in the

response message.

The Data section contains arbitrary values.
A CRC-16 value is generated from a calculation including the message slave address, function code, test code, and data. The procedure for

calculating a CRC-16 is described at the end of this chapter. When the slave receives the command message it calculates a CRC-16 value and

compares it to the CRC-16 of the command message. If the two CRC-16 values are identical and the Slave Address is correct, the slave

processes command message. If the two CRC-16 values are not identical, the slave will discard the command message and not respond.
If the command message has a valid slave address, function code, test code, data and CRC-16, the slave will respond with the normal response

message. If the command message has an invalid function code, test code, and/or data, the slave will respond with a fault response message. If

the command message has an invalid slave address or CRC-16, no response will be returned.