Operation method and frequency reference, Operation method and frequency reference -8, Operation method – Yaskawa F7 Modbus User Manual

Page 13: Frequency reference source, Connections 1-8

Advertising
background image

Connections 1-8

Operation Method and Frequency Reference

The Run/Stop and Frequency Reference commands can originate from serial communication, the operator keypad, external terminals, or an

option card. Parameter b1-01 (Operation Method Selection) allows the selection of the origin of the Run/Stop command. Parameter b1-02

(Reference Selection) allows the selection of the origin of the Frequency Reference command. The Run/Stop and Frequency Reference

commands may have different origins. For example, the Run/Stop command may be set to External Terminals (b1-01 = 1) while the Frequency

Reference command may be set Serial Communications (b1-02=2).

Operation Method

Table 1.7 – Operation Method Selection

b1-01

Operation Method Selection (Run/Stop)

0 Operator

keypad

1

External Terminals (Default setting is 1)

2 Serial

Communication

3 Option

Card

4 Pulse

Input

Frequency Reference Source

Table 1.8 – Frequency Reference Source Selection

b1-02

Frequency Reference Selection

0 Operator

keypad

1

External Terminals (Default setting is 1)

2

Serial Communications (Parameter Access)

3 Option

Card