F7U Parameters 4-25

Parameter Dependencies

Certain F7 drive parameters, Master parameters, can affect the default values, range of values and accessibility of other, dependent,

parameters. When a Master parameter’s value is changed via serial communications (RS232, RS485, DeviceNet, Ethernet, etc.,), the

associated dependent parameters are not automatically updated and must be updated serially. For example, parameter d2-02 (frequency

lower limit) affects the range of values for all frequency reference parameters (d1-01 through d1-17). If d2-02 is changed to 5.0 Hz serially,

all frequency reference parameters with values below 5.0 Hz must be updated serially to have current values of 5.0 Hz or greater. An F7

drive fault may occur if a dependent parameter’s value is not updated.
The standard sequence for changing F7 drive parameters is

Set A1-01 to 2 - Set the access value to Advanced

Set Master parameter to desired value

Send ENTER command

Set any dependent parameter values

Send ENTER command.

Master Parameter Sequence Numbers

Some F7 drive parameters may be dependent on more than one Master parameter. For example o2-04 (kVA) and o2-09 (specification)

affect a number of parameters together. In these cases it is necessary that the parameter with the lowest sequence number be changed first.

The sequence table is shown below. Sequence numbers range From 1 through 9 with lower sequence parameters being changed before

parameters with higher sequence numbers. In all cases the parameter access level (o2-09) should be changed first.

Table 4.18 – Master Parameter Sequence Numbers

Prm

Seq

Name

Action after parameter change

Send ENTER command, power cycle F7 drive, change dependent parameters, send ENTER

o2-09

2

Initialization Mode

WARNING

Possible personal injury and/or damage to equipment may occur if o2-09 setting is change

from 1 (American Spec). o2-09 is a macro parameter that can change the default values of

terminal I/O and many other parameters. Consult with Yaskawa factory for details.

If o2-09 is also to be changed, set o2-09 before setting dependent or slave parameter values.

o2-04

1

kVA or F7 drive Model

A1-02 3 Control

Method

C1-10 5

Acc/Dec

Time

Units

C6-01 4

Heavy/Normal

Duty

C6-02 5

Carrier

Frequency

d2-01

5

Freq Upper Limit

d2-02

5

Freq Lower Limit

E1-01 5

Input

Voltage

L3-04

5

Stall Prevention @ DEC

L4-01 5

Speed

Agree

Detection

Level

L4-02

5

Speed Agree Detection Width

L4-03 5

Speed

Agree

Detection

Level

±

L4-04

5

Speed Agree Detection Width

±

L4-05

5

Operation @ Frequency Loss Detection

L8-02

5

Overheat Pre-Alarm Level

L8-15

5

OL2 @ Low Speed

All

Others

9

Send

master

parameter

Send

ACCEPT

Change dependent parameters

Send

ACCEPT