Modbus tcp/ip dpram interface (read / write), Modbus tcp/ip dpram interface (read / write) -2, F7u parameters 4-2 – Yaskawa F7 Modbus User Manual

Page 41

Advertising
background image

F7U Parameters 4-2

MODBUS TCP/IP DPRAM Interface (Read / Write)

A maximum of 10 simultaneous connections are allowed.

The RUN Command and Frequency Reference may only be accessed through UNIT ID 1. While the drive is in remote RUN

mode, the RUN command must be continually refreshed within 5 seconds. If the RUN command is not refreshed within 5

seconds, an EF0 fault will occur. Refer to the appropriate drive manual for information on EF0 and setting the appropriate drive

response. If a UNIT ID 1 connection is active, the NS/CON LED will blink at approximately a 500 ms cycle.

The TCP/IP connection must be refreshed within 60 seconds. If it is not refreshed within 60 seconds, the connection will be

closed.

This implementation of MODBUS TCP/IP supports MODBUS functions 3 (read multiple registers), 6 (write single register) and

16 (write multiple registers).

The table below lists those registers available via high speed DP-RAM. DP-RAM access is designed to be used as part of the

standard PLC I/O or scan table, where fast response is required. Other register values should be accessed via individual messages,

i.e. via an MSTR block.

Table 4.2 – MODBUS TCP/IP Interface Registers

Addr

Function

Bit

Description

0h

Forward RUN Input

1h Reverse

RUN

Input

2h

Multi-Function Digital Input S3

3h

Multi-Function Digital Input S4

4h

Multi-Function Digital Input S5

5h

Multi-Function Digital Input S6

6h

Multi-Function Digital Input S7

7h

Multi-Function Digital Input S8 (G5, F7 & G7 only)

8h

External Fault Input (EF0)

9h Fault

Reset

Ah

Multi-Function Digital Input S9 G7 only)

Bh

Multi-Function Digital Input S10 G7 only)

Ch

Multi-Function Digital Input S11 G7 only)

Dh

Multi-Function Digital Input S12 G7 only)

Eh

Fault Log Trace Clear Input

0001h Command

Fh

External Base Block Input

0002h Frequency Reference

Frequency Reference

0h

@ RUN

1h

@ Zero Speed

2h

@ Reverse RUN

3h

@ Reset

4h

@ Speed Agree

5h

@ Drive Ready

6h

@ Minor Fault

7h

@ Major Fault

8h

@ OPE Fault

9h

@Return From Sudden Stop

Ah

@ Remote Mode

Bh

Multi-Function Output 1

Ch

Multi-Function Output 2

Dh

Multi-Function Output 3 (G5, F7 & G7 only)

Eh

@ Motor 2 Selected

2000h

Status

Fh

@ Zero Servo Complete

2001h

Speed

U1-05

2002h

Torque

U1-09

2003h

PG Count Channel 1

PG Count Channel 1

2004h

Frequency Reference

U1-01

2005h

Output Frequency

U1-02

2006h

Current

U1-03

2007h

Terminal 14 Output

Terminal 14 Output

2008h

DC BUS Voltage

DC BUS Voltage

0h

PUF Fuse

Fault

1h

UV1 Main

Circuit

Undervoltage

2h

UV2 Control Power Undervoltage

3h

UV3 MC

Fail

4h

Reserved

5h

GF Ground

Fault

6h

OC Overcurrent

7h

OV Overvoltage

8h

OH Drive

Overheat

9h

OH1 Motor

Overheat

Alarm

Ah

OL1 Motor

Overload

Bh

OL2 Drive

Overload

Ch

OL3 Overtorque

1

Dh

OL4 Overtorque

2

2009h

Error 1

Eh

RR Braking

Resistor

Fault