F7U Parameters 4-20

Table 4.11 – H Parameters

Mode

Name

Addr

Digital Operator

Text

Data

Parameter Range or

Data Description

Inc

Default

Run

V/f

V/f

wPG

OLV

FV

Dep

0

Ramp to Stop

1

Coast to Stop

2 Fast-Stop

H5-04

0428h

Serial Fault Sel

3 Alarm

Only

1

3

A A A A

0 Disabled

H5-05

0429h

Serial Flt Dtct

1 Enabled

1

1

A A A A

H5-06

042Ah

Transmit WaitTIM

5 ~ 65 ms

1 ms

5 ms

A

A

A

A

0 Disabled

H5-07

042Bh

RTS Control Sel

1 Enabled

1

1

A A A A

0 Frequency

Ref

1 PI

Feedback

H6-01

042Ch

Pulse Input Sel

2

PI Set Point

1

0

A A A A

H6-02

042Dh

Pulse In Scaling

1000 ~ 32000 Hz

1 Hz

1440 Hz

R

A

A

A

A

H6-03

042Eh

Pulse Input Gain

0.0 ~ 1000.0 %

0.1 %

100.00 %

R

A

A

A

A

H6-04

042Fh

Pulse Input Bias

-100.0 ~ 100.0 %

0.1 %

0.00 %

R

A

A

A

A

H6-05

0430h

Pulse In Filter

0.0 ~ 2.0 Sec

0.01 Sec

0.1 Sec

R

A

A

A

A

H6-06

0431h

Pulse Moni Sel

See H4-01

1

02h

R

A

A

A

A

H6-07

0432h

Pulse Moni Scale

0 ~ 32000 Hz

1 Hz

1440 Hz

R

A

A

A

A

L Parameters - Protection

Table 4.12 – L Parameters

Mode

Name

Addr

Digital Operator

Text

Data

Parameter Range or

Data Description

Inc

Default

Run

V/f

V/f

wPG

OLV

FV

Dep

0 120

Hz

1 180

Hz

2 Custom

V/F

L1-01 0480h MOL

Fault

Select

3

Custom w/o limit

1

1

Q Q Q Q

L1-02

0481h

MOL Time Const

0.1 ~ 5.0 min

0.1 min

1.0 min

A

A

A

A

0

Ramp to Stop

1

Coast to Stop

2 Fast-Stop

L1-03

0482h

Mtr OH Alarm Sel

3 Alarm

Only

1

3

A A A A

0

Ramp to Stop

1

Coast to Stop

L1-04

0483h

Mtr OH Fault Sel

2 Fast-Stop

1

1

A A A A

L1-05

0484h

Mtr Temp Filter

0.0 ~ 10.0 Sec

0.01 Sec

0.2 Sec

A

A

A

A

0 Disabled
1

PwrL RideThru t

L2-01 0485h

PwrL

Selection

2

CPU Power Active

1

0

A A A A

L2-02

0486h

PwrL Ridethru t

0.0 ~ 25.5 Sec

0.1 Sec

0.1 Sec

A

A

A

A

L2-03

0487h

PwrL Baseblock t

0.1 ~ 5.0 Sec

0.1 Sec

0.5 Sec

A

A

A

A

L2-04

0488h

PwrL V/F Ramp t

0.0 ~ 5.0 Sec

0.1 Sec

0.3 Sec

A

A

A

A

L2-05

0489h

PUV Det Level

150 ~ 210 VDC

1 VDC

190 VDC

A

A

A

A

A1-02

L2-06

048Ah

KEB Decel Time

0.0 ~ 200.0 Sec

0.1 Sec

0.0 Sec

A

A

A

A

L2-07

048Bh

UV Return Time

0.0 ~ 25.5 Sec

0.1 Sec

0.0 Sec

A

A

A

A

L2-08

048Ch

KEB Frequency

0 ~ 300 %

100 %

A

A

A

A

0 Disabled
1 General

Purpose

L3-01

048Fh

StallP Accel Sel

2 Intelligent

1 1

A

A

A

NA

L3-02

0490h

StallP Accel Lvl

0 ~ 200 %

1 %

150 %

A

A

A

NA

L3-03

0491h

StallP CHP Lvl

0 ~ 100 %

1 %

50 %

A

A

A

NA

0 Disabled
1 General

Purpose

2 Intelligent

L3-04

0492h

StallP Decel Sel

3

Stall prev w/R

1

1

Q Q Q Q

0 Disabled
1

Decel Time 1

L3-05

0493h

StallP Run Sel

2

Decel Time 2

1 1

A

A

NA

NA

L3-06

0494h

StallP Run Level

30 ~ 200 %

1 %

160 %

A

A

NA

NA

0 Disabled

L3-11 04C7h

OV

Inhibit

Sel

1 Enabled

1 0

NA

NA

A

A

L3-12

04C8h

OV Inhbt VoltLvl

350 ~ 390 V

1 V

380 V

NA

NA

A

A

A1-02

L4-01

0499h

Spd Agree Level

0.0 ~ 400.0 Hz

0.1 Hz

0.0 Hz

A

A

A

A

C6-01

L4-02

049Ah

Spd Agree Width

0.0 ~ 20.0 Hz

0.1 Hz

2.0 Hz

A

A

A

A

L4-03

049Bh

Spd Agree Lvl+-

-400.0 ~ 400.0 Hz

0.1 Hz

0.0 Hz

A

A

A

A

C6-01

L4-04

049Ch

Spd Agree Wdth+-

0.0 ~ 20.0 Hz

0.1 Hz

2.0 Hz

A

A

A

A

0 Stop

L4-05 049Dh

Ref

Loss

Sel

1

Run@ 80 % PrevRef

1

0

A A A A

L4-06

04C2h

Fref at Floss

0.0 ~ 100.0 %

0.1 %

80.00 %

A