Write single register normal response message, Write single register fault response message – Yaskawa F7 Modbus User Manual

Page 22

Advertising
background image

Message Formats 2-5

Write Single Register Normal Response Message

Table 2.6 - Write Registers Normal Response Message

Description

Data

Slave Address

01h

Function Code

06h

Upper

00h

Register Address

Lower

01h

Upper

00h

Data

Lower

03h

Upper

98h

CRC-16

Lower

0Bh

The normal response message contains the same slave address, function code, register address and data as the command message, indicating to

the master, which slave is responding and to what type of function it is responding.
In the response message above the register address is 01h (0001h).

Write Single Register Fault Response Message

Table 2.7 - Write Registers Fault Response Message

Description

Data

Slave Address

01h

Function Code

86h

Error Code

21h

Upper

82h

CRC-16

Lower

78h

The fault response message contains the same slave address as the command message, indicating to the master which slave is responding.

The function code of a fault response message is the logical OR of 80h and the original function code of 06h. This indicates to the master that the

message is a fault response message, instead of a normal response message.
The error code indicates where the error occurred in the command message. The value of 21h in the error code field of this fault response

message indicates that the command message data to be written was invalid for that register. Refer to the section Error Codes, Table 2-14, for

more information on returned error codes.