Message Formats 2-1

Protocol

The parameter access method supported by the Yaskawa F7 drive is a subset of the MODBUS

®

communication protocol. The F7 drive supports

functions 3, 6, 8 and 10h. The message format varies depending upon the function code of the message. For each function code, there is a

command message from the master and a response message from the slave. The following sections review the format of the command and

response messages for each function.

Message Functions Supported

The following table lists the function codes available and their minimum and maximum lengths.

Table 2.1 - Supported Function Codes

Command Message

Response Message (Normal)

Function Code

Function

min. (bytes)

max. (bytes)

min. (bytes)

max. (bytes)

3h (3 dec)

Read Multiple Registers

8

8

7

21

6h (6 dec)

Write Single Register

8

8

8

8

8h (8 dec)

Loop-Back test

8

8

8

8

10h (16 dec)

Write Multiple Registers

11

25

8

8