8.1 System Configuration and Connection Example for SERVOPACK with Fully-closed Loop Control

8-11

8

Fu

lly-close

d L

oop

Co

ntro

l

To output the phase-C pulse when a detection point is passed in reverse, set the following parameter to 1.

Note: When using a serial converter unit, Phase-C pulse is output in forward and reverse direction regardless of the setting

in Pn081.

Parameter

Meaning

When Enabled

Classification

Pn081

n.

0

[Factory Setting]

Outputs phase-C pulse only in forward direction.

After restart

Setup

n.

1

Outputs phase-C pulse in forward and reverse
direction.

Setting of Pn081.0
Do not change the factory setting if the zero point position of the existing equipment must
remain as is.

• When Pn081.0 = 1, the width of the phase-C pulse output is narrower than that of the

phase-A pulse in some cases.

• As shown in the following figure, there is a one-eighth scale pitch difference in posi-

tions between the two settings (Pn081.0 = 1 and Pn081.0 = 0) for the phase-C pulse
output, the zero point return command, and the phase-C detection by phase-C latch
function.

1/8

scale pitch

Pn081.0 =

0

Zero point

Zero point

Moves to forward

1 scale pitch

Pn081.0 =

1