10 Appendix

10.1.2 Parameters

10-20

Pn511

2

Input Signal Selection 5

0000 to

FFFF

6541

After restart

Setup

3.4.1

(cont’d)

Parameter

No.

Size

Name

Setting

Range

Units

Factory

Setting

When

Enabled

Classi-

fication

Reference

Section

Input Signal 1 Mapping for Command Option Module (/SI1)

0

Active when CN1-40

input signal is ON (closed).

1

Active when CN1-41

input signal is ON (closed).

2

Active when CN1-42

input signal is ON (closed).

3

Active when CN1-43

input signal is ON (closed).

4

Active when CN1-44

input signal is ON (closed).

5

Active when CN1-45 input signal is ON (closed).

6

Active when CN1-46 input signal is ON (closed).

7

Always active (fixed).

8

Not active (fixed).

9

Active when CN1-40 input signal is OFF (open).

A

Active when CN1-41 input signal is OFF (open).

B

Active when CN1-42

input signal is OFF (open).

C

Active when CN1-43

input signal is OFF (open).

D

Active when CN1-44 input signal is OFF (open).

E

Active when CN1-45 input signal is OFF (open).

F

Active when CN1-46

input signal is OFF (open).

Input Signal 4 Mapping for Command Option Module (/SI4)

4

Active when CN1-44 input signal is ON (closed).

5

Active when CN1-45 input signal is ON (closed).

6

Active when CN1-46 input signal is ON (closed).

7

Always active (fixed).

8

Not active (fixed).

D

Active when CN1-44 signal is OFF (open).

E

Active when CN1-45 signal is OFF (open).

F

Active when CN1-46 signal is OFF (open).

0 to 3

9 to C

Not active (fixed).

Input Signal 5 Mapping for Command Option Module (/SI5)

4 to 8

D to F

Same as /SI4 signal mapping.

Input Signal 6 Mapping for Command Option Module (/SI6)

4 to 8

D to F

Same as /SI4 signal mapping.

4th 3rd 2nd 1st

digit digit digit digit

n.