9 Troubleshooting

9.1.2 Troubleshooting of Alarms

9-22

FL-1

*2

:

System Alarm

A fault occurred in the SERVO-
PACK.

−

Turn the power supply OFF and

then ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

FL-2

*2

:

System Alarm

CPF00:
Digital Operator

Transmission Error 1

The contact between the digital
operator and the SERVOPACK is
faulty.

Check the connector contact.

Insert securely the connector or
replace the cable.

Malfunction caused by noise
interference.

−

Keep the digital operator or the
cable away from noise sources.

CPF01:
Digital Operator
Transmission Error 2

A digital operator fault occurred.

−

Disconnect the digital operator and
then re-connect it. If the alarm still
occurs, the digital operator may be
faulty. Replace the digital operator.

A fault occurred in the SERVO-

PACK.

−

Turn the power supply OFF and
then ON again. If the alarm still

occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

∗2. These alarms are not stored in the alarm history and are displayed only in the panel display.

(cont’d)

Alarm Number:

Alarm Name

(Alarm Description)

Cause

Investigative Actions

Corrective Actions