9 Troubleshooting

9.1.2 Troubleshooting of Alarms

9-22

FL-1

*2

:

System Alarm

A fault occurred in the SERVO-
PACK.

Turn the power supply OFF and

then ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

FL-2

*2

:

System Alarm

CPF00:
Digital Operator

Transmission Error 1

The contact between the digital
operator and the SERVOPACK is
faulty.

Check the connector contact.

Insert securely the connector or
replace the cable.

Malfunction caused by noise
interference.

Keep the digital operator or the
cable away from noise sources.

CPF01:
Digital Operator
Transmission Error 2

A digital operator fault occurred.

Disconnect the digital operator and
then re-connect it. If the alarm still
occurs, the digital operator may be
faulty. Replace the digital operator.

A fault occurred in the SERVO-

PACK.

Turn the power supply OFF and
then ON again. If the alarm still

occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

∗2. These alarms are not stored in the alarm history and are displayed only in the panel display.

(cont’d)

Alarm Number:

Alarm Name

(Alarm Description)

Cause

Investigative Actions

Corrective Actions