MVI56-101S ♦ ControlLogix Platform

Reference

IEC 60870-5-101 Slave Communication Module

User Manual

ProSoft Technology, Inc.

Page 101 of 193

August 2, 2011

Read Block

This block transfers IEC output (control) data sent from the remote IEC 104
Client through the module to the ControlLogix processor. The following table
outlines the structure of data contained in the input image of a normal Read
Block
.

Offset Description

Length

0

Reserved

1

1

Write Block ID

1

2 to 201

Read Data

200

202

Program Scan Counter

1

203 to 204

Product Code

2

205 to 206

Product Version

2

207 to 208

Operating System

2

209 to 210

Run Number

2

211 to 214

Data Transfer Status

4

215

Port Select

1

216

Bad Checksum Count

1

217

Sync Error Count

1

218

Length Error Count

1

219

Timeout Error Count

1

220

RX Frame Count

1

221

TX Frame Count

1

222 to 248

Spare

27

249

Read Block ID

1

The Read Block ID is an index value sent by the module and used by the ladder
logic to determine where the current 200-word block of input data should be
placed in the ControlLogix processor IEC870S.ReadData controller tag array.
Each input data block transfer can move up to 200 words of user application data
(Read Block offsets 2 to 201) from the module to the processor. In addition to
moving user data, the block also contains module status data. This status data is
transferred with each new input image block and can be used for module
diagnostics.