ProSoft Technology MVI56-101S User Manual

Page 160

Advertising
background image

Reference MVI56-101S

♦ ControlLogix Platform

User Manual

IEC 60870-5-101 Slave Communication Module

Page 160 of 193

ProSoft Technology, Inc.

August 2, 2011

5.6

MVI56-101S Error Status Table

This section contains a listing of the MVI56-101S module's status data area. This
file is located at the MVI56-101S database starting at address 4000. You may
also configure an additional area using the "Error Offset" parameter.

Offset Parameter Description

4000 Scan

Count

This status value contains a counter incremented on each
scan of the module's main loop.

4001 to 4002 Product Name

This two-word data area contains the text values representing
the product name.

4003 to 4004 Revision

This two-word data area contains the text values for the
revision number.

4005 to 4006 Op Sys #

This two-word data area contains the text values for the
operating system number.

4007 to 4008 Run Number

This two-word data area contains the text values for the run
number.

4009

Read Blk Cnt

This word contains the total number of block read operations
successfully executed.

4010

Write Blk Cnt

This word contains the total number of block write operations
successfully executed.

4011

Parse Blk Cnt

This word contains the total number of write blocks
successfully parsed.

4012

Error Blk Cnt

This word contains the total number of block transfer errors.

4013 Port

Selected

This parameter determines which port on the module is being
utilized. If the value is set to 0, the primary port is being used.
If the value is set to 1, the backup port is being utilized.

4014 Bad

CKS This word contains the total number of frames received by the

module that contain a bad check-sum values in the message.

4015 Sync

Errors

This word contains the total number of frames received by the
module that have synchronization errors. Each frame in the
protocol has a specific header that must be received in a fixed
sequence. If this header is not received correctly, this word will
be incremented, and the frame will be discarded.

4016 Length

Errors

This word contains the total number of frames received by the
module that do not have the correct length.

4017 Timeout This word contains the total number of frames received by the

module that were not received within the specified receive
timeout parameter.

4018 RX

Frames

This word contains the total number of frames received by the
module.

4019 TX

Frames

This word contains the total number of frames transmitted by
the module.

4020

MSP Event Buffer This parameter shows the number of events available in the

event buffer for M_SP_NA points.

4021

MDP Event Buffer This parameter shows the number of events available in the

event buffer for M_DP_NA points

4022

MST Event Buffer This parameter shows the number of events available in the

event buffer for M_ST_NA points

4023

MMENA Event
Buffer

This parameter shows the number of events available in the
event buffer for M_ME_NA points

4024

MMENB Event
Buffer

This parameter shows the number of events available in the
event buffer for M_ME_NB points